How to Choose the Right Generator for Your Refrigerated or Freezer Trailer

R&D Logo_edited.png

How to properly size a portable generator for your refrigerated or freezer trailer. Understand running watts, compressor startup requirements, and the differences between 120V and 220V refrigeration systems to ensure reliable cooling when shore power isn't available.

A portable generator is an excellent way to operate your refrigerated trailer when traditional electrical hookups are unavailable. Whether you're using your trailer at a festival, farmers market, outdoor event, remote jobsite, or temporary storage location, selecting the correct generator is essential for dependable refrigeration.

Not all generators are suitable for operating refrigeration equipment. Choosing a generator that is too small can cause issues with the refrigeration system related to voltage drops, electrical interruptions, and potential equipment damage.


Understanding Generator Wattage

When selecting a generator, there are two important electrical ratings to understand:

Running Watts (Rated Watts)- This represents the amount of electrical power a generator can continuously supply while operating.

Starting Watts (Surge Watts)- This is the amount of power the generator is able to supply as a short burst of extra power for a few seconds to start things like electric motors.


Keep in mind your generator needs sufficient capacity to start the compressor while also supplying power to other electrical components, like the evaporator fans, lights, and other accessories and equipment, if installed.

Not all manufacturers rate & sell their generators in the same way. Some manufactures that sell a generator as a 5500W model are rated based on the running watts, while others will rate it as starting watts, so make sure to read through the specs carefully.


Important Takeaway: A generator that provides enough power to keep a compressor running may still be unable to start it.


Why Compressor Startup Matters

When a refrigeration compressor starts, its motor must accelerate from a complete stop to normal operating speed while trying to compress the refrigerant gas at the same time. Think of it as not only trying to run a 60 yard dash, but doing so while pulling a parachute too. During this brief period, the compressor can draw significantly more electrical current than it does while running, up to several times higher than the current requored during normal operation. 

Locked rotor amperage (LRA) is not the same as the actual startup current under every operating condition. It is an important indicator of starting demand, but the generator's ability to start the compressor also depends on motor characteristics, startup duration, voltage regulation, and the generator's surge capability.

Ultimatly, a generator must be able to handle the compressor's starting requirements without excessive voltage drop.


Choosing Between a Conventional and Inverter Generator

There are two primary types of portable generators available: conventional generators and inverter generators. While both can operate a refrigerated trailer when properly sized, there are several important differences in how they produce electricity and respond to changing electrical demands.


Inverter Generators

Inverter generators use a more advanced method of producing electricity. The generator initially produces AC electricity, converts it into direct current (DC), and then electronically converts it back into controlled AC electricity. This process allows the generator to maintain a consistent electrical frequency without requiring the engine to operate at a constant speed. 

Because refrigeration equipment cycles on and off throughout the day, an inverter generator can reduce its engine speed when the compressor is not operating and increase its speed when additional power is required. Inverter generators are generally an excellent choice for refrigerated trailer applications and is what we recommend.


Inverter Generator Advantages:

  • More consistent voltage and electrical frequency.

  • Typically produces cleaner electrical power.

  • Improved fuel efficiency under partial loads.

  • Quieter operation in many cases.

  • Reduced engine speed during periods of low electrical demand.

  • Well suited for electronic refrigeration controls and digital thermostats.

Inverter Generator Disadvantages:

  • Higher purchase cost.

  • More complex electronic components.

  • Potentially more expensive repairs.

  • Some models have limited short-duration motor-starting capacity.

  • Economy mode may interfere with compressor startup on certain models.

Inverters in Economy Mode vs Compressor Startup 

One important consideration when using an inverter generator is its economy mode (sometimes referred to as Eco Mode or Smart Throttle). Economy mode allows the generator to reduce its engine speed when electrical demand is low, conserving fuel and reducing noise. However, when a refrigeration compressor suddenly starts, the generator must respond almost immediately to the increased electrical demand. If the generator cannot increase its output quickly enough, it may experience a voltage drop or enter overload protection. For this reason, disabling economy mode may be necessary when operating refrigeration equipment, particularly when the generator is operating near its maximum starting capacity.

Note that an inverter generator is not guarenteed to have better motor-starting capabilities than a conventional generator. There are some conventional generators that are better equipped to handle brief, high-current demands due to their alternator design and rotating mass.


Conventional Generators

Conventional generators can also operate refrigeration equipment when properly sized. However, some generators experience significant voltage drops when large motors start. Conventional generators produce power through a direct engine-driven alternator. Most conventional portable generators operate at a constant engine speed of approximately 3,600 RPM to maintain a 60 Hz electrical frequency.

When a refrigeration compressor starts, the sudden increase in electrical demand places a significant load on the generator. This can cause a temporary reduction in engine speed, voltage, and electrical frequency until the generator compensates for the additional load.

Higher-quality conventional generators typically incorporate an Automatic Voltage Regulator (AVR) to help maintain consistent output voltage.


Convential Generator Advantages:

  • Lower initial purchase cost.

  • Greater power output per dollar.

  • Available in larger power capacities.

  • Generally simpler construction and easier repair.

  • Some models offer excellent motor-starting capabilities.

Conventional Generator Disadvantages:

  • Generally louder during operation.

  • Higher fuel consumption under lighter electrical loads.

  • Potentially higher total harmonic distortion (THD).

  • Greater potential for voltage and frequency fluctuations.

  • Typically operates at a constant engine speed, regardless of refrigeration demand.


A generator advertised as producing 240V does not automatically guarantee compatibility with every trailer electrical system. The generator's output configuration, receptacle, neutral connection, and current capacity must match the trailer's electrical requirements.


Other Electrical Loads to Consider

The refrigeration compressor is usually the largest electrical load, but it is not necessarily the only one.

Depending on your trailer's configuration, you need to take into consideration all additional electrical equipment needs, which may include:

  • Standard LED interior lights & the evaporators require approx 2A.

  • Optional exterior lighting

  • Optional interior outlets and their devices or equipment using them

  • Optinoal exterior outlets and their devices or equipment using them

These loads must be included when determining total generator capacity.


Refrigeration Equipment Used in Our Trailers

R&D Refrigerated Trailers utilizes two main condensing units. The first and most commonly used is our 120V 3/4hp condensing unit. This unit has the following specs:

  • Compressor rated load current: 14 amps

  • Compressor locked rotor current: 56 amps

  • Minimum circuit ampacity: 20 amps

  • Nema 5-15P plug on cord

The second is our larger 220V 1-1/2hp condensing unit. This is commonly used on refrigerated trailers over 16' long and on our freezer trailers. This unit has the following specs:

  • Compressor rated load current: 18 amps

  • Compressor locked rotor current: 75 amps

  • Minimum circuit ampacity: 24 amps

  • L14-30 plug on cord


Additional Considerations When Choosing a Generator


Generator Output

Pay attention to the generator's continuous rated output, not just the starting-wattage number advertised by the manufacturer.


Fuel Capacity and Runtime

Consider how long the trailer needs to operate between refueling. A generator that can power the refrigeration system for several hours may not be practical for an event requiring continuous operation throughout the day. Thankfully, R&D Refrigerators has solutions to increase un-interrupted runtime and is able to get 24hr+ run times out of generators. Send us a message or give us a call to find out more.


Can You Use a Generator That Is "Too Large"?

There are no issues uing a generator with more capacity than your refrigeration system requires. Having additional capacity allows for running other equipment off it later on down the road and does not harm the refrigeration equipment since the refrigeration system draws the electrical power it needs & the generator does not force its full rated wattage into the trailer. 

The downside to this is with excessively large generators, it will increase your upfront purchase costs, they are typically larger and heavier, and often consume more fuel, depending on the generator design and operating load.


Final Recommendations

When choosing a generator for your R&D Refrigerated Trailer, remember these important points:

  1. Confirm which refrigeration condensing unit your trailer uses.

  2. Select a generator with the correct voltage and electrical output configuration.

  3. Consider both continuous running power and compressor startup demand.

  4. Include any additional electrical equipment in your calculations.

  5. Choose a generator with sufficient reserve capacity for reliable operation.

  6. Verify that the generator can start the refrigeration compressor under actual operating conditions.

Generators we would recommend considering:

Budget:

Kobalt R5500P 5500W Inverter Generator https://www.lowes.com/pd/Kobalt-Kobalt-49-State-6830-5500-Watt-Gasoline-Portable-Generator/5016279743


Mid:

Champion 201238 6500W Inverter Generator https://www.championpowerequipment.com/product/201238-6500w-inverter/

Champion 201169 6500W Conventional Generator https://www.championpowerequipment.com/product/201169-6500w-electric-start-tri-fuel-generator-with-co-shield

Generac GP5500E Conventional Generator https://www.generac.com/residential-products/portable-generators/5500-portable-generator-with-cosense-50st-8150/


High End:

Honda EM6500SX Conventional Generator https://powerequipment.honda.com/generators/models/em6500

Honda EU7000iS Inverter Generator https://powerequipment.honda.com/generators/models/eu7000is



Disclaimer: we are not associated or endorsed by any of these brands, nor do we recieve compensation in any way. These are strictly based on our experiences and published specs from the manufacturer.